DevEN is a high-performance, scriptable power system simulation library designed for rapid power flow, short-circuit, contingency analysis, and time-series automation. All core computational engines are compiled to high-speed native binary extensions (.pyd) for maximum execution speed and intellectual property protection.
Install via pip:
pip install devenWhen you install deven, all required dependencies (numpy, scipy, pandas, networkx, openpyxl, prettytable, typing_extensions) are automatically installed.
DevEN seamlessly ingests power system models across multiple standard file formats:
| Format | Extension | Description |
|---|---|---|
| Python Case Database | .py |
Native dictionary-based power network model |
| SQL Database | .sql, .sqlite, .db |
Relational SQLite database container |
| Raw Grid Data | .raw |
Standard ASCII bus/branch power network file |
| DGS General Schema | .dgs, .pfd |
General schema data exchange file |
| Tabular Network Data | .dat, .dat0 |
Fixed-column tabular network data file |
DevEN provides four primary study modules:
-
Load Flow Analysis (LFA)
- High-performance Newton-Raphson solver (
deven_nr) - Configurable tolerance (default
1e-5) and iterations (default30) - Detailed generation, load, branch flow, voltage magnitude, and loss calculations
- Automatic IEEE, CEA, and KCL compliance reporting
- High-performance Newton-Raphson solver (
-
Short Circuit Studies (SCS)
- Standard-compliant fault calculations (IEC 60909)
- Three-phase symmetrical faults (3-Ph) and single line-to-ground faults (SLG)
- Initial symmetrical short-circuit current (
$I_k''$ ), peak current ($i_p$ ), and breaking current ($I_b$ )
-
Contingency Analysis (CA)
- Comprehensive N-1, N-k, and user-defined multi-element contingencies
- Outage simulation for transmission lines and power transformers
- Island detection and post-contingency voltage/thermal limit violations
-
Time Series Load Flow (TS-LFA)
- Multi-period time-domain simulation (e.g. 24-hour profiles)
- Hourly or sub-hourly dispatch steps
- Time-series voltage profiles, branch loadings, and loss accumulation
import deven
# Initialize stateful simulation session
sess = deven.DevENSession()
# Load power system case (.py, .sql, .raw, .dgs, or .dat)
sess.load_case("case.py")
# 1. Run Load Flow Analysis
lfa_res = sess.run_lfa(engine="deven_nr", tol=1e-5, max_iter=30)
print(f"LFA Converged: {lfa_res['converged']} in {lfa_res['iterations']} iterations")
# 2. Run Short Circuit Analysis (IEC 60909)
scs_res = sess.run_scs(method="iec")
print(f"SCS Calculated: {scs_res['buses_calculated']} buses evaluated")
# 3. Run Contingency Analysis (Outage of specific lines & transformers)
ca_res = sess.run_ca(
lines=[1, 2, 3, 4],
transformers=[1, 2],
engine="deven_nr"
)
print(f"CA Evaluated: {ca_res['total_contingencies']} cases")
# 4. Run 24-Hour Time Series Load Flow
ts_res = sess.run_timeseries(
duration=24.0,
dur_unit="Hours",
step_size=1.0,
step_unit="Hours",
engine="deven_nr"
)
print(f"Time Series Completed: {ts_res['steps_completed']} steps")This project is licensed under the MIT License — see the LICENSE file for details.
DevEN (Develop Electric Network) is an ultra-fast, scriptable AC power flow and grid analysis engine developed by Devaraj E & team, Bengaluru (ಬೆಂಗಳೂರು), India. DevEN features native C/C++ compiled mathematical kernels (compiled to .pyd extensions) for maximum execution speed and intellectual property protection. It is designed to replace slow, expensive commercial power system tools for rapid prototyping, automation, scripting, and large-scale batch simulation.
The free tier supports up to 100 buses. Commercial licensing is available for unlimited bus counts.
Contact: devarajedeva2002@gmail.com
- 📖 Docs / GitHub Pages: https://deven-ps.github.io/DevEN/
- ⭐ GitHub Repository: https://github.com/DevEN-PS/DevEN
- 📄 Master PDF Manual: DevEN_Master_User_and_API_Reference_Manual.pdf
Calculates steady-state bus voltage magnitudes (V), phase angles (θ), active/reactive power flows (P, Q), and system losses. Uses Newton-Raphson (NR), Fast-Decoupled (FDLF), Gauss-Seidel (GS), Levenberg-Marquardt (LM), and Continuation Power Flow (CPF) solvers.
Standards: IEEE 399 / IEEE 3004.2 / IEC 60909-0
sess.run_lfa(engine="deven_nr", tol=1e-5, max_iter=30)Solves full coupled 3-phase nodal equations (Y_abc × V_abc = I_abc) for unbalanced distribution grids. Calculates neutral voltage rise (Vn), phase loadings, Voltage Unbalance Factor (VUF%).
Standards: IEEE Std 1159 / NEMA MG 1 / IEC 61000-4-30
sess.run_3ph_lfa()IEC 60909 and ANSI/IEEE C37 fault calculations. Initial symmetrical short-circuit current (Ik''), peak current (ip), breaking current (Ib), DC offset. Supports 3-Ph, SLG, LL, DLG fault types.
Standards: IEC 60909-0 / ANSI/IEEE C37.010
sess.run_scs(method="iec")N-1, N-k, and user-defined multi-element contingency simulation for lines and transformers. Island detection, post-contingency thermal/voltage violations.
Standards: NERC TPL / IEEE 3006
sess.run_ca(lines=[1,2,3], transformers=[1])Multi-period time-domain simulation (24-hour, 8760-hour annual). Hourly/sub-hourly dispatch. Time-series voltage profiles, branch loadings, loss accumulation stored in SQLite.
sess.run_timeseries(duration=24.0, step_size=1.0)Minimizes total generation cost ($/MWh) subject to power flow equations, voltage limits, thermal limits, and generator MW/MVAr capability constraints. KKT interior point and IPOPT solvers.
sess.run_opf(obj="min_cost")Computes PV nose curves and QV curves. Reports voltage stability index (VSI), maximum loadability (Pmax), critical operating points.
Standards: IEEE Std 1110 / IEC 60038
sess.run_vsa(bus=5, direction="load")Calculates bus voltage dip (ΔV%) during induction motor DOL, star-delta (Y-Δ), and soft-starter transients. NEMA MG 1 voltage dip limit compliance.
Standards: IEEE 399 / IEC 60034-12
sess.run_mss(motor_bus=12, hp=1500, method="dol")Injects harmonic current spectra (orders 3, 5, 7, 11, 13…) from VFDs/UPS/arc furnaces. Solves harmonic bus voltages, reports THD%.
Standards: IEEE 519-2022 / IEC 61000-3-6
sess.run_hlf(harmonic_orders=[3,5,7,11,13])OCR, DOCR, differential, and distance relays. TCC plots, coordination margins (CTI ≥ 0.3 s), selectivity gap detection.
Standards: IEEE Std 242 (Buff Book) / IEC 60255
sess.run_pcs(relay_type="ocr", curve="IEC_EI")Earth fault currents for solidly/resistance/reactance grounded and ungrounded systems. Ground potential rise (GPR), step/touch voltages, grounding adequacy.
Standards: IEEE Std 80 / IEC 60364
sess.run_gfs(grounding="resistance", Rg=40.0)Voltage sags, swells, flicker (Pst, Plt), THD, TDD, power factor, unbalance. Reports against IEEE 519, EN 50160, IEC 61000-4-30.
sess.run_pqs(metrics=["thd","pf","flicker"])Maximum continuous ampacity of underground cables and overhead conductors per IEC 60287 and IEEE 835. Accounts for soil thermal resistivity, installation depth, burial grouping, ambient temperature.
sess.run_cat(cable_id=3, soil_rho=1.0, depth=0.9)Time-domain swing equation integration with generator dynamic models (Classical, GENROU, AVR exciter) after fault clearing. Critical clearing time (CCT), rotor angle trajectories, speed deviations.
Standards: IEEE Std 1110
sess.run_tss(fault_bus=3, fault_dur=0.1)TTC and ATC (= TTC − TRM − ETC − CBM) for transmission corridors. FERC Order 888 compliance and open-access tariff studies.
Standards: NERC MOD-001 / NERC TPL
sess.run_ttc(from_area=1, to_area=2)Optimal locations/sizes for reactive compensation (shunt capacitors, SVCs, STATCOMs) to minimize losses, improve voltage profiles, maximize loadability. Sensitivity-based (∂Q/∂V) and mixed-integer optimization.
sess.run_rpp(method="sensitivity")| Engine ID | Method | Convergence | Best For |
|---|---|---|---|
deven_nr |
Newton-Raphson | Quadratic | Transmission networks, general use |
deven_fdlf |
Fast-Decoupled (XB/BX) | Linear per sub-problem | Large systems, high X/R ratio |
deven_gs |
Gauss-Seidel | Linear | Small radial distribution networks |
deven_lm |
Levenberg-Marquardt | Quadratic (robust) | Ill-conditioned, heavily loaded grids |
deven_cpf |
Continuation Power Flow | Predictor-corrector | Voltage stability nose curves |
DevEN supports a comprehensive set of power system elements modelled from first principles:
| Element | Key Parameters |
|---|---|
| Bus | Slack / PV / PQ / Isolated types; V-pu, angle, kV base |
| Generator | MW, MVAr, Vset, Pmin/Pmax, Qmin/Qmax, droop |
| Load | Constant power (ZIP), constant current, constant impedance, motor loads |
| Transmission Line | Pi-model: R, X, B/2 per unit or ohm/km; thermal rating (MVA) |
| 2-Winding Transformer | YY, YD, DD, ZigZag; OLTC, ULTC, phase shifting |
| 3-Winding Transformer | Star equivalent; primary/secondary/tertiary MVA ratings and impedances |
| Shunt Capacitor/Reactor | Fixed/switched MVAr; harmonic filter C-R-L banks |
| SVC / STATCOM | Voltage-controlled reactive injection; slope and deadband |
| Induction Motor | Equivalent circuit (Rs, Xs, Rr, Xr, Xm, slip); starting curve |
| Harmonic Source | Current injection model; VFD, UPS, arc furnace spectra |
| Wind / Solar PV | Type 3/4 DFIG, full-converter PV inverter; FRT capability |
| Battery Storage (BESS) | 4-quadrant inverter; SOC model; charge/discharge scheduling |
Active and Reactive Power Injection at Bus i:
P_i = Σ_j |V_i||V_j| (G_ij cos θ_ij + B_ij sin θ_ij)
Q_i = Σ_j |V_i||V_j| (G_ij sin θ_ij − B_ij cos θ_ij)
Short Circuit — Initial Symmetrical Current (IEC 60909):
I_k'' = c × V_n / (√3 × |Z_k|)
Cable Ampacity (IEC 60287):
I = √[ (Δθ − W_d[0.5T₁ + n(T₂+T₃+T₄)]) / (T₁·R + n(1+λ₁)T₂·R + n(1+λ₁+λ₂)(T₃+T₄)·R) ]
Voltage Unbalance Factor (VUF):
VUF% = (|V₋₋₋| / |V₊₊₊|) × 100
deven run-lfa grid.dss --engine deven_nr --tol 1e-6 --max-iter 50 --output results.db3
deven run-scs grid.raw --method iec --fault-bus 5 --fault-type slg --output scs.xlsx
deven run-ca grid.json --contingencies n1 --monitor voltage thermal --output ca_report.pdf
deven run-ts grid.xlsx --duration 8760 --step 1.0 --profile load_profile.csv --output ts.db3
deven info # print version, license status, bus count limit
deven license activate --key <YOUR_KEY> # unlock unlimited buses| Standard | Scope |
|---|---|
| IEC 60909-0:2016 | Short-circuit currents in three-phase AC systems |
| IEC 60287 | Electric cables — current ratings |
| IEC 61000-3-6 / 4-30 | Harmonics & power quality |
| IEEE 519-2022 | Harmonic control in power systems |
| IEEE 399 / 3004.2 | Power system analysis & load flow |
| IEEE Std 242 (Buff Book) | Protection & coordination |
| IEEE Std 80 | Grounding of AC substations |
| NERC TPL / MOD-001 | Transmission planning standards |
| NEMA MG 1 | Motors and generators |
| EN 50160 | Voltage characteristics of public electricity supply |
| FERC Order 888 | Open-access transmission tariff |
| IEC 60034-12 | Rotating electrical machines — starting performance |