Develop Electric Network - This tool is used to do Load Flow Studies

Resources

Stars

3 stars

Watchers

0 watching

Forks

Repository files navigation

DevEN Power System Analysis Engine & Python Library

PyPI version Python versions License: MIT

DevEN is a high-performance, scriptable power system simulation library designed for rapid power flow, short-circuit, contingency analysis, and time-series automation. All core computational engines are compiled to high-speed native binary extensions (.pyd) for maximum execution speed and intellectual property protection.


⚡ Installation

Install via pip:

pip install deven

When you install deven, all required dependencies (numpy, scipy, pandas, networkx, openpyxl, prettytable, typing_extensions) are automatically installed.


📁 Supported Input File Formats

DevEN seamlessly ingests power system models across multiple standard file formats:

Format Extension Description
Python Case Database .py Native dictionary-based power network model
SQL Database .sql, .sqlite, .db Relational SQLite database container
Raw Grid Data .raw Standard ASCII bus/branch power network file
DGS General Schema .dgs, .pfd General schema data exchange file
Tabular Network Data .dat, .dat0 Fixed-column tabular network data file

🔬 Core Capabilities

DevEN provides four primary study modules:

  1. Load Flow Analysis (LFA)

    • High-performance Newton-Raphson solver (deven_nr)
    • Configurable tolerance (default 1e-5) and iterations (default 30)
    • Detailed generation, load, branch flow, voltage magnitude, and loss calculations
    • Automatic IEEE, CEA, and KCL compliance reporting
  2. Short Circuit Studies (SCS)

    • Standard-compliant fault calculations (IEC 60909)
    • Three-phase symmetrical faults (3-Ph) and single line-to-ground faults (SLG)
    • Initial symmetrical short-circuit current ($I_k''$), peak current ($i_p$), and breaking current ($I_b$)
  3. Contingency Analysis (CA)

    • Comprehensive N-1, N-k, and user-defined multi-element contingencies
    • Outage simulation for transmission lines and power transformers
    • Island detection and post-contingency voltage/thermal limit violations
  4. Time Series Load Flow (TS-LFA)

    • Multi-period time-domain simulation (e.g. 24-hour profiles)
    • Hourly or sub-hourly dispatch steps
    • Time-series voltage profiles, branch loadings, and loss accumulation

🚀 Quickstart Example

import deven

# Initialize stateful simulation session
sess = deven.DevENSession()

# Load power system case (.py, .sql, .raw, .dgs, or .dat)
sess.load_case("case.py")

# 1. Run Load Flow Analysis
lfa_res = sess.run_lfa(engine="deven_nr", tol=1e-5, max_iter=30)
print(f"LFA Converged: {lfa_res['converged']} in {lfa_res['iterations']} iterations")

# 2. Run Short Circuit Analysis (IEC 60909)
scs_res = sess.run_scs(method="iec")
print(f"SCS Calculated: {scs_res['buses_calculated']} buses evaluated")

# 3. Run Contingency Analysis (Outage of specific lines & transformers)
ca_res = sess.run_ca(
    lines=[1, 2, 3, 4],
    transformers=[1, 2],
    engine="deven_nr"
)
print(f"CA Evaluated: {ca_res['total_contingencies']} cases")

# 4. Run 24-Hour Time Series Load Flow
ts_res = sess.run_timeseries(
    duration=24.0,
    dur_unit="Hours",
    step_size=1.0,
    step_unit="Hours",
    engine="deven_nr"
)
print(f"Time Series Completed: {ts_res['steps_completed']} steps")

This project is licensed under the MIT License — see the LICENSE file for details.


🌐 About DevEN — Develop Electric Network

DevEN (Develop Electric Network) is an ultra-fast, scriptable AC power flow and grid analysis engine developed by Devaraj E & team, Bengaluru (ಬೆಂಗಳೂರು), India. DevEN features native C/C++ compiled mathematical kernels (compiled to .pyd extensions) for maximum execution speed and intellectual property protection. It is designed to replace slow, expensive commercial power system tools for rapid prototyping, automation, scripting, and large-scale batch simulation.

The free tier supports up to 100 buses. Commercial licensing is available for unlimited bus counts.
Contact: devarajedeva2002@gmail.com


🔬 All 16 Power System Studies

1. 1-Phase Load Flow Analysis (LFA)

Calculates steady-state bus voltage magnitudes (V), phase angles (θ), active/reactive power flows (P, Q), and system losses. Uses Newton-Raphson (NR), Fast-Decoupled (FDLF), Gauss-Seidel (GS), Levenberg-Marquardt (LM), and Continuation Power Flow (CPF) solvers.
Standards: IEEE 399 / IEEE 3004.2 / IEC 60909-0

sess.run_lfa(engine="deven_nr", tol=1e-5, max_iter=30)

2. 3-Phase Unbalanced Load Flow (3P LFA)

Solves full coupled 3-phase nodal equations (Y_abc × V_abc = I_abc) for unbalanced distribution grids. Calculates neutral voltage rise (Vn), phase loadings, Voltage Unbalance Factor (VUF%).
Standards: IEEE Std 1159 / NEMA MG 1 / IEC 61000-4-30

sess.run_3ph_lfa()

3. Short Circuit Study (SCS)

IEC 60909 and ANSI/IEEE C37 fault calculations. Initial symmetrical short-circuit current (Ik''), peak current (ip), breaking current (Ib), DC offset. Supports 3-Ph, SLG, LL, DLG fault types.
Standards: IEC 60909-0 / ANSI/IEEE C37.010

sess.run_scs(method="iec")

4. Contingency Analysis (CA)

N-1, N-k, and user-defined multi-element contingency simulation for lines and transformers. Island detection, post-contingency thermal/voltage violations.
Standards: NERC TPL / IEEE 3006

sess.run_ca(lines=[1,2,3], transformers=[1])

5. Time Series Load Flow (TS-LFA)

Multi-period time-domain simulation (24-hour, 8760-hour annual). Hourly/sub-hourly dispatch. Time-series voltage profiles, branch loadings, loss accumulation stored in SQLite.

sess.run_timeseries(duration=24.0, step_size=1.0)

6. Optimal Power Flow (OPF)

Minimizes total generation cost ($/MWh) subject to power flow equations, voltage limits, thermal limits, and generator MW/MVAr capability constraints. KKT interior point and IPOPT solvers.

sess.run_opf(obj="min_cost")

7. Voltage Stability Analysis (VSA)

Computes PV nose curves and QV curves. Reports voltage stability index (VSI), maximum loadability (Pmax), critical operating points.
Standards: IEEE Std 1110 / IEC 60038

sess.run_vsa(bus=5, direction="load")

8. Motor Starting Study (MSS)

Calculates bus voltage dip (ΔV%) during induction motor DOL, star-delta (Y-Δ), and soft-starter transients. NEMA MG 1 voltage dip limit compliance.
Standards: IEEE 399 / IEC 60034-12

sess.run_mss(motor_bus=12, hp=1500, method="dol")

9. Harmonic Load Flow (HLF)

Injects harmonic current spectra (orders 3, 5, 7, 11, 13…) from VFDs/UPS/arc furnaces. Solves harmonic bus voltages, reports THD%.
Standards: IEEE 519-2022 / IEC 61000-3-6

sess.run_hlf(harmonic_orders=[3,5,7,11,13])

10. Protection Coordination Study (PCS)

OCR, DOCR, differential, and distance relays. TCC plots, coordination margins (CTI ≥ 0.3 s), selectivity gap detection.
Standards: IEEE Std 242 (Buff Book) / IEC 60255

sess.run_pcs(relay_type="ocr", curve="IEC_EI")

11. Ground Fault Study (GFS)

Earth fault currents for solidly/resistance/reactance grounded and ungrounded systems. Ground potential rise (GPR), step/touch voltages, grounding adequacy.
Standards: IEEE Std 80 / IEC 60364

sess.run_gfs(grounding="resistance", Rg=40.0)

12. Power Quality Study (PQS)

Voltage sags, swells, flicker (Pst, Plt), THD, TDD, power factor, unbalance. Reports against IEEE 519, EN 50160, IEC 61000-4-30.

sess.run_pqs(metrics=["thd","pf","flicker"])

13. Cable Ampacity & Thermal Rating (CAT)

Maximum continuous ampacity of underground cables and overhead conductors per IEC 60287 and IEEE 835. Accounts for soil thermal resistivity, installation depth, burial grouping, ambient temperature.

sess.run_cat(cable_id=3, soil_rho=1.0, depth=0.9)

14. Transient Stability Study (TSS)

Time-domain swing equation integration with generator dynamic models (Classical, GENROU, AVR exciter) after fault clearing. Critical clearing time (CCT), rotor angle trajectories, speed deviations.
Standards: IEEE Std 1110

sess.run_tss(fault_bus=3, fault_dur=0.1)

15. Total Transfer Capability (TTC/ATC)

TTC and ATC (= TTC − TRM − ETC − CBM) for transmission corridors. FERC Order 888 compliance and open-access tariff studies.
Standards: NERC MOD-001 / NERC TPL

sess.run_ttc(from_area=1, to_area=2)

16. Reactive Power Planning (RPP)

Optimal locations/sizes for reactive compensation (shunt capacitors, SVCs, STATCOMs) to minimize losses, improve voltage profiles, maximize loadability. Sensitivity-based (∂Q/∂V) and mixed-integer optimization.

sess.run_rpp(method="sensitivity")

⚙️ Solvers & Engines

Engine ID Method Convergence Best For
deven_nr Newton-Raphson Quadratic Transmission networks, general use
deven_fdlf Fast-Decoupled (XB/BX) Linear per sub-problem Large systems, high X/R ratio
deven_gs Gauss-Seidel Linear Small radial distribution networks
deven_lm Levenberg-Marquardt Quadratic (robust) Ill-conditioned, heavily loaded grids
deven_cpf Continuation Power Flow Predictor-corrector Voltage stability nose curves

🏗️ Element Library

DevEN supports a comprehensive set of power system elements modelled from first principles:

Element Key Parameters
Bus Slack / PV / PQ / Isolated types; V-pu, angle, kV base
Generator MW, MVAr, Vset, Pmin/Pmax, Qmin/Qmax, droop
Load Constant power (ZIP), constant current, constant impedance, motor loads
Transmission Line Pi-model: R, X, B/2 per unit or ohm/km; thermal rating (MVA)
2-Winding Transformer YY, YD, DD, ZigZag; OLTC, ULTC, phase shifting
3-Winding Transformer Star equivalent; primary/secondary/tertiary MVA ratings and impedances
Shunt Capacitor/Reactor Fixed/switched MVAr; harmonic filter C-R-L banks
SVC / STATCOM Voltage-controlled reactive injection; slope and deadband
Induction Motor Equivalent circuit (Rs, Xs, Rr, Xr, Xm, slip); starting curve
Harmonic Source Current injection model; VFD, UPS, arc furnace spectra
Wind / Solar PV Type 3/4 DFIG, full-converter PV inverter; FRT capability
Battery Storage (BESS) 4-quadrant inverter; SOC model; charge/discharge scheduling

📐 Key Power Flow Equations

Active and Reactive Power Injection at Bus i:

P_i = Σ_j |V_i||V_j| (G_ij cos θ_ij + B_ij sin θ_ij)
Q_i = Σ_j |V_i||V_j| (G_ij sin θ_ij − B_ij cos θ_ij)

Short Circuit — Initial Symmetrical Current (IEC 60909):

I_k'' = c × V_n / (√3 × |Z_k|)

Cable Ampacity (IEC 60287):

I = √[ (Δθ − W_d[0.5T₁ + n(T₂+T₃+T₄)]) / (T₁·R + n(1+λ₁)T₂·R + n(1+λ₁+λ₂)(T₃+T₄)·R) ]

Voltage Unbalance Factor (VUF):

VUF% = (|V₋₋₋| / |V₊₊₊|) × 100

💻 CLI Quick Reference

deven run-lfa  grid.dss  --engine deven_nr --tol 1e-6 --max-iter 50 --output results.db3
deven run-scs  grid.raw  --method iec --fault-bus 5 --fault-type slg --output scs.xlsx
deven run-ca   grid.json --contingencies n1 --monitor voltage thermal --output ca_report.pdf
deven run-ts   grid.xlsx --duration 8760 --step 1.0 --profile load_profile.csv --output ts.db3
deven info                     # print version, license status, bus count limit
deven license activate --key <YOUR_KEY>   # unlock unlimited buses

📋 Standards & Compliance Reference

Standard Scope
IEC 60909-0:2016 Short-circuit currents in three-phase AC systems
IEC 60287 Electric cables — current ratings
IEC 61000-3-6 / 4-30 Harmonics & power quality
IEEE 519-2022 Harmonic control in power systems
IEEE 399 / 3004.2 Power system analysis & load flow
IEEE Std 242 (Buff Book) Protection & coordination
IEEE Std 80 Grounding of AC substations
NERC TPL / MOD-001 Transmission planning standards
NEMA MG 1 Motors and generators
EN 50160 Voltage characteristics of public electricity supply
FERC Order 888 Open-access transmission tariff
IEC 60034-12 Rotating electrical machines — starting performance